14. Design patterns ​

Small arrangements of blocks that solve problems you meet in every plant. Each is used in the examples. Where hakkas works differently from a PLC, the pattern says why.

14.1 Choosing between signals ​

Choose between two values by a condition: process/SelectIn. output is in_true while select is true, else in_false. Used for:

  • the thermostat's setpoint, 21 or 17 °C (Section 4.8);
  • the heat exchanger's 100 % or 0 % by the fans (Section 13.6).

Add an offset by a condition: a SelectIn choosing between 0 and the offset, then a math/Add2. Used for the heating circuit's night setback (Section 12.2).

Choose one of up to eight: process/MultiplexIn, with select 1–8. For example, a mode selector: 1 comfort, 2 economy, 3 frost guard.

Route one value to one of several places: process/SelectOut (two) or process/MultiplexOut (eight). The outputs not chosen are 0, not their last value, so a downstream actuator never keeps running on a stale value.

The larger or the smaller of several: math/Max and math/Min. Used where two regulators share an actuator and the one asking more must win, as frost protection and the supply air both drive the heating valve (Section 13.6). Only the inputs that are fed count.

A manual override: process/AutoMan. override makes output follow manual instead of input. The output jumps when switched. For a regulator, use the PID's own auto and manual instead: that switch is bumpless.

Coming from IEC 61131-3

SelectIn is SEL, MultiplexIn is MUX counting from 1, and math/Max and math/Min are MAX and MIN, except that unconnected inputs do not count.

14.2 Latches ​

Set and reset by edges: process/Trigger. A rising fire sets output, and a rising arm clears it. Only edges count, so a held button acts once. It is the latch of Extended operation (Section 13.3).

Set and reset by levels, an SR flip-flop: a logic/Or fed back through a logic/And, with reset winning:

A set-reset latch: an Or fed back through an And

This is a feedback loop: the And's output goes back to the Or. Section 14.8 explains when such a loop is safe. This one is safe, since each block changes only once per change of set or reset.

A latch held by an alarm: often what needs latching is "until a person has acknowledged". process/Alarm is such a latch, with proper states. The air handling unit's frost lock is the alarm not being Normal (Section 13.7).

Coming from IEC 61131-3

There are no SR/RS blocks: process/Trigger is the edge-triggered latch. R_TRIG/F_TRIG are rarely needed, since only changes travel. A block that acts on a rising edge, such as Trigger, Alarm's acknowledge or a calendar boundary, does so itself.

14.3 Timers ​

PLC timerIn hakkas
on-delay TONprocess/Delay with mode 1: on waits, off passes at once
off-delay TOFprocess/Delay with mode 2: off waits, on passes at once
on- and off-delay togetherprocess/Delay with mode 0, its resting value: output takes input once it has been stable for milliseconds
pulse TP (a fixed-length pulse)process/Trigger fired by the input, armed by a process/Delay of its own output (the pattern of Section 13.3)
a pulse train, a blinkertiming/Interval: a period and a duty cycle
a debounceprocess/Delay of a few hundred ms: a shorter pulse never comes through
running hoursprocess/Integrator of the running signal (1 while true), divisor 3600

Times in units: a process/Delay and a timing/Interval take milliseconds. timing/Days, timing/Hours, timing/Minutes and timing/Seconds convert, so a process reads as it is meant: 3 → Hours → Delay.

A process/Delay's time and mode can be changed while it waits, and the change applies to the running wait. The AHU uses that to end Extended operation and reset at once (Section 13.3).

Timers run on the controller's clock and survive nothing: a stop or a restart starts them from zero (14.7).

14.4 Schedules and calendars ​

Schedules are built from calendar blocks, each true while the current time matches its setting, joined by logic:

BlockSettingExample
timing/MinuteRangeHH:MM-HH:MM06:00-18:00, or 22:00-06:00 over midnight
timing/DayOfWeekdays 1–7, Monday = 11-5 workdays, 6,7 weekends
timing/DayOfMonthdays 1–311 the first of each month
timing/MonthOfYearmonths 1–1210-4 October to April
timing/DayOfYeardays 1–366
timing/WeekOfYearISO weeks 1–5328-31 the summer holiday

Settings are lists and ranges: 1-3,5, and a range may wrap: 6-1 is Saturday to Monday.

A week schedule is a MinuteRange and a DayOfWeek (the thermostat, Section 4.8). The standard library has it, and the day, month and year schedules, as composite types (schedule/WeekSchedule, …; Chapter 16 installs it).

Several periods a day: one MinuteRange per period, joined by logic/Or.

Dates (15 September – 15 May): whole months, plus the parts of the first and last month, as the AHU's seasons do (Section 13.4).

Exceptions, such as holidays: a DayOfYear or WeekOfYear with the exception days, used to switch the schedule off through a logic/And with a logic/Not. Holidays that move, such as Easter, need their days updated each year.

The blocks use the controller's local time, from its time-zone setting, including daylight saving time (Section 16.2). They wake exactly at their boundaries, and nothing polls.

14.5 Scaling to and from volts ​

Keep the process in engineering units, and convert at the edges with process/Linear (out = k·in + m):

Signalkm
0–100 % to 0–10 V0.10
0–100 % to 2–10 V0.082
0–10 V from a sensor of −50…+50 °C10−50
4–20 mA from a sensor of 0…10 bar0.625−2.5

A regulator then works in percent, and only the scaling knows the valve's signal. Put the scaling next to the binding, so that the process reads in units.

For a non-linear sensor, use process/Curve with up to seven points from its data sheet.

14.6 Alarm handling ​

process/Alarm follows a condition: a bool, true while the alarmed situation exists. It keeps the alarm's state until a person acknowledges it:

  • Activated when the condition comes;
  • Deactivated when it goes, unacknowledged;
  • Acknowledged when acknowledged while it still holds;
  • back to Normal when both have happened;
  • Reactivated when it comes back unacknowledged.

Good conditions:

  • Delay them. A process/Delay with mode 1 before the alarm keeps a passing deviation from raising it, and lets the alarm go as soon as the condition does. For a slow process the wait is long: 2 → Hours → Delay before "the room has not reached its setpoint". The AHU's frost waits 5 s, with both edges delayed.

  • Alarm on goals, not on components: the temperature that is not reached, rather than every status contact (Section 13.12).

  • Give it a class:

    • A: attend to at once, day and night;
    • B: during working hours;
    • C: soon;
    • D: of interest only.

    Give it a category (the unit's name), so that alarm views can sort them.

  • Use the states. A function that must wait for acknowledgement uses the alarm's outputs. The AHU's frost lock is "not Normal".

  • Fluttering: an alarm that comes and goes all the time can be blocked for a while (block); one that must not raise at all is disabled (disable).

Acknowledging is a rising edge on acknowledge: a button on the unit, or an input set from elsewhere.

14.7 Start-up behaviour ​

A process that starts, whether because you started it or because the controller restarted after a power cut, starts afresh:

  • Every block computes once from its inputs as they are, and sends all its outputs. Then the values travel as usual.
  • Sensors deliver a moment later. Until then, a bound input holds its resting value: 0 °C for a temperature.
  • Nothing is remembered: timers start from zero, integrals from their manual values, latches and alarms from off. There are no retained variables.

Patterns for it:

  • A start delay for regulators. A PID that goes to automatic before its measurement has arrived presets its integral from a bogus error. Give it a start delay:

    1. A fixed value true into a process/Delay with mode 1, its time from 10 → Seconds.
    2. A logic/And of the delay's output and the regulator's other conditions, into auto.

    In mode 1 a Delay starts with its output false, and a true input waits the full time, also one that is there at the start. In mode 0 it takes its input at once at the start, so there a fixed true would pass at once (Section 12.5).

  • Confirm conditions that a missing value can fake. A frost alarm on "below 5 °C" fires at the start on the sensor's resting 0 °C. A delay before it avoids that (Section 13.8). With mode 1 even a condition that is true at the start waits.

  • Count on a safe resting state. Every input rests at 0 or false, and the block types are designed so that rest means off: a regulator in manual at 0, a schedule off, a pump off. A process with a missing connection does nothing, rather than something wrong.

  • Stopping keeps the outputs. A stopped process does not switch its actuators off. If an actuator must be off during maintenance, switch it off from within the process, for example with a maintenance switch on the operator's panel, and then stop.

  • Remembering across restarts is not possible yet. A value that must survive, such as a counter or a setpoint changed by an operator, belongs in a fixed value that is saved with the process.

Coming from IEC 61131-3

There is no warm start and no RETAIN: every start is a cold start. Design the process so that a cold start is safe, which the resting values make the natural case.

14.8 Ordering in feedback loops ​

All changes go through one queue and are worked off in the order they arise (Section 2.2). Without feedback the order does not matter: each block computes when an input changes, and the last change it sees wins.

With feedback, where a block's output comes back to one of its own inputs through other blocks, the order can matter:

  • A loop that settles, like the SR latch of 14.2, is safe. Each change travels round once, and the blocks then hold.
  • A loop that never settles, such as a logic/Not fed by its own output, oscillates as fast as the queue can work it off. It does not deadlock, but it keeps the controller busy. Break every such loop with something that holds: a process/Delay, a process/Trigger, or a timer.
  • A loop whose result depends on which of two changes arrives first is a design error. The usual case is two paths from one change that meet again in one block, which then computes twice: once with the new value from the short path and the old one from the long path, then with both new. The intermediate output travels on. If that matters, for example to a latch, delay or confirm the result, or rework the logic so that one path decides.

The AHU's Extended operation is a loop that settles. The timer's own output changes its time, and when it turns true the time becomes 0, so the timer follows its input back at once (Section 13.3).

Coming from IEC 61131-3

A PLC evaluates a network once per cycle in a fixed order, and a feedback variable is read with last cycle's value. In hakkas every change propagates at once and completely, so a loop runs until it settles, not once per cycle.